Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/22/2011

Applicant:

FOOD CONSPIRACY

Description:

Full Fire Prevention Inspection Building Rep: Bradford Trojans Phone # 903-0038

Outstanding Inspections

Case Number: T11FR00893
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
04/22/2011 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
04/22/2011 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) ____________________________ (Captain) Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you.