Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

04/18/2011

Applicant:

PIERETTI MC DONALDS LLC

Description:

Full inspection done 4/18/2011 / A2 occupancy / Magda Garcia - manager / 749-4777

Outstanding Inspections

Case Number: T11FR00855
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/18/2011 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations:
04/18/2011 VIOL - ADMINISTRATION BCOBB Violation Door latch coming apart: UNSAFE BUILDINGS 110.1 General. If during the inspection of a premises, a building or structure or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section and shall refer the building to the building department for any repairs, alterations, remodeling, removing or demolition required. 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. A vacant structure which is not secured against unauthorized entry as required by Section 311 shall be deemed unsafe. ______ Fix back door latch / handle - screws are coming out.
04/18/2011 VIOL - EMERGENCY PLAN/PREPARE BCOBB Violation Employees knowledge of "Pull Station": TFC2006/ 406.3.3 Fire safety training. Employees assigned fire-fighting duties shall be trained to know the locations and proper use of portable fire extinguishers or other manual fire-fighting equipment and the protective clothing or equipment required for its safe and proper use. ______Hold a "safety"class for all employees on the location and use of the "pull station" for the hood system, and other topics such as chaining gas bottles, clear exits, etc. Have a roster of attendees with the date, subjects covered, and instructor, for my review. [Note: It is a good idea to revisit this information periodically at your employee meetings.]
04/18/2011 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation Extinguishers not mounted: TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. [K class]
04/18/2011 VIOL - MEANS OF EGRESS BCOBB Violation Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights.
04/18/2011 VIOL - COMPRESSED GASES BCOBB Violation Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner.