Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

04/12/2011

Applicant:

WRI MADERA VILLAGE LLC

Description:

Full inspection done 4/12/2011; Dawn Gerhart - owner; 749-0277

Outstanding Inspections

Case Number: T11FR00825
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/12/2011 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations:
04/12/2011 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner (per the Electrical Code). [outlet above hopper in back room]
04/12/2011 VIOL - MEANS OF EGRESS BCOBB Violation Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. [one by front door]