Case: T11FR00807
Case Details
Entered Date:
04/08/2011
Applicant:
ADMINISTRATIVE ADDRESSES
Description:
Walgreens fire inspction.
Outstanding Inspections
Case Number: T11FR00807
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
04/08/2011 | VIOL - COMPRESSED GASES | JLOYA | Violation | 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel. *** Secure gas cylinder in an approved manner to avoid accidental dislodgment. |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00807
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2011 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
04/26/2011 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |