Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/08/2011

Applicant:

FURBER DEVELOPMENT

Description:

Big Five fire inspection.

Outstanding Inspections

Case Number: T11FR00806
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/08/2011 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/08/2011 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
04/08/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report.
04/08/2011 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00806
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/26/2011 INSP - REINSPECTION JLOYA Approved Violatiions abated.