Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

03/30/2011

Applicant:

BABKA INVESTMENTS LLC

Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T11FR00748
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
03/30/2011 INSP - FULL jdavis Correction Required 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 2. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied - Provide back up power supply for all required exit illumination 3. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: 4. _____ 3405.3.6.2Listed and approved machines. Parts cleaning and degreasing conducted in listed and approved machines in accordance with Section 3405.3.6.1 shall be in accordance with Sections 3405.3.6.2.1 through 3405.3.6.2.7. - provide solder links and all safety components for your parts cleaners (2 each)