Case: T11FR00727
Case Details
Entered Date:
03/29/2011
Applicant:
AMERICAN MEAT COMPANY
Description:
Panaderia Real fire inspection.
Outstanding Inspections
Case Number: T11FR00727
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2011 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 03/29/2011 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. |
| 03/29/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 609.2 Where required, A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. |
| 03/29/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
| 03/29/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
| 03/29/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00727
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2011 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |