Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/24/2011

Applicant:

TITH SOPHAL & SIP SOMALY CP/RS

Description:

Big L Market fire inspection.

Outstanding Inspections

Case Number: T11FR00701
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/24/2011 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. Building < 50 feet from the curb require 12" numbers displayed on the building. Buildings > 50 feet from the curb require 15" numbers displayed on the building. Tenant space numbers shall be 3" Address range may be displayed in 12" numbers on the building.
03/24/2011 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
03/24/2011 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00701
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/24/2011 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
06/08/2011 INSP - REINSPECTION JLOYA Approved Violations abated.