Case: T11FR00679
Case Details
Entered Date:
03/22/2011
Applicant:
PASS-A-GRILLE REALTY COMPANY
Description:
Bartlett Tree Experts 3/21/11
Outstanding Inspections
Case Number: T11FR00679
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2011 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards |
03/22/2011 | VIOL - HAZARDOUS MATERIALS,GEN | MPursley | Correction Required | 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____Place NFPA 704 marking on front and back of building and Conex box |
03/22/2011 | VIOL - FLAMMABLE LIQUIDS | MPursley | Correction Required | 3404.3.4.4 Liquids for maintenance and operation of equipment. In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 3404.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet when in approved containers located in private garages or other approved locations. _____Place fuel in Flammable liquids cabinet. |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00679
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2011 | INSP - REINSPECTION | MPursley | Approved | All corrections made 6/1/11 |