Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/22/2011

Applicant:

PASS-A-GRILLE REALTY COMPANY

Description:

Bartlett Tree Experts 3/21/11

Outstanding Inspections

Case Number: T11FR00679
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/22/2011 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards
03/22/2011 VIOL - HAZARDOUS MATERIALS,GEN MPursley Correction Required 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____Place NFPA 704 marking on front and back of building and Conex box
03/22/2011 VIOL - FLAMMABLE LIQUIDS MPursley Correction Required 3404.3.4.4 Liquids for maintenance and operation of equipment. In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 3404.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet when in approved containers located in private garages or other approved locations. _____Place fuel in Flammable liquids cabinet.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00679
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/02/2011 INSP - REINSPECTION MPursley Approved All corrections made 6/1/11