Case: T11FR00664
Case Details
Entered Date:
03/21/2011
Applicant:
SK INC
Description:
Waste Oil
Outstanding Inspections
Case Number: T11FR00664
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2011 | INSP - UST | CFUNKE | Correction Required | 03-17-2011 Shell 880 West Saint Mary's Tucson, AZ Dear Sir or Madam, The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 03-15-2011. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. The waste oil tank must either be placed in service and monitored or be placed in a temporary closure status upon completion of the requirements below. 3404.2.13.1 Underground tanks. Underground tanks taken out of service shall comply with Sections 3404.2.13.1.1 through 3404.2.13.1.5. 3404.2.13.1.1 Temporarily out of service. Underground tanks temporarily out of service shall have the fill line, gauge opening, vapor return and pump connection secure against tampering. Vent lines shall remain open and be maintained in accordance with Sections 3404.2.7.3 and 3404.2.7.4. 3404.2.13.1.2 Out of service for 90 days. Underground tanks not used for a period of 90 days shall be safeguarded in accordance with all the following or be removed in accordance with Section 3404.2.14: 1. Flammable or combustible liquids shall be removed from the tank. 2. All piping, including fill line, gauge opening, vapor return and pump connection, shall be capped or plugged and secured from tampering. 3. Vent lines shall remain open and be maintained in accordance with Sections 3404.2.7.3 and 3404.2.7.4. 3404.2.13.1.3 Out of service for one year. Underground tanks that have been out of service for a period of one year shall be removed from the ground in accordance with Section 3404.2.14 Re-Inspected by __________________ Approved Disapproved Sincerely, Conrad Funke Fire Inspector Tucson Fire Department (520) 837-7111 |