Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/17/2011

Applicant:

FLORES KARIME GUTIERREZ

Description:

Doggy Day Care 3/16/11

Outstanding Inspections

Case Number: T11FR00657
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - REINSPECTION None Not Inspected
03/17/2011 VIOL - ADMINISTRATION MPursley Correction Required 102.4 Application of building code. The design and construction of new structures shall comply with the International Building Code, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. A Certificate of Occupancy shall be provided To obtain a Certificate of Occupancy or a replacement copy, contact the city of Tucson Development services Department (DSD) located at 201 N. Stone, (520) 791-5550.
03/17/2011 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____place "NO Exit" sign on blocked doors
03/17/2011 VIOL - FIRE RESIST.RATED CONST MPursley Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile
03/17/2011 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards
03/17/2011 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress doors, as bolt lock of any kind are not permitted

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00657
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/05/2011 COMPL - REINSPECTION MPursley Approved All corrections made 4/13/11