Case: T11FR00656
Case Details
Entered Date:
03/17/2011
Applicant:
DOSS LIVING TRUST
Description:
requesting fire inspection. contact: Annie 622-7676, call first.
Outstanding Inspections
Case Number: T11FR00656
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2011 | INSP - FULL | RDUARTE | Continued | requesting fire inspection. |
| 04/25/2011 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile _____ Fix and repair all openings or holes in the ceiling |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00656
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2011 | COMPL - REINSPECTION | MPursley | Approved | All corrections made |