Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/15/2011

Applicant:

JH 6226 LLC

Description:

Burger king fire inspection.

Outstanding Inspections

Case Number: T11FR00633
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
03/15/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
03/15/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00633
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/15/2011 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/01/2011 INSP - REINSPECTION JLOYA Approved Violations abated.