Description:

United Fire system report: multiple hood deficiencies, rpt in log book.

Outstanding Inspections

Case Number: T11FR00624
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
03/29/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ___At leat one link or heat detector shall be installed above each cooking appliance. ___All penetrations of the hood shall have a liquid tight continuos weld or sealed by a listed devise. ____Manual activation devices shall be a minimum of 10 ft and no more than 20ft from the system.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00624
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/29/2011 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/14/2011 INSP - REINSPECTION JLOYA Approved Violations abated.