Description:

Milligan's Auto Repair 3/8/11

Outstanding Inspections

Case Number: T11FR00579
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/09/2011 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the back office egress door, as bolt lock of any kind are not permitted
03/09/2011 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times
03/09/2011 VIOL - FLAMMABLE LIQUIDS MPursley Correction Required 3403.5 Labeling and signage. The fire code official is authorized to require warning signs for the purpose of identifying the hazards of storing or using flammable liquids. Signage for identification and warning such as for the inherent hazard of flammable liquids or smoking shall be provided in accordance with this chapter and Sections 2703.5 and 2703.6. _____Label 55gal. barrels 3404.2.7 Design, construction and general installation requirements for tanks. The design, fabrication and construction of tanks shall comply with NFPA 30. Each tank shall bear a permanent nameplate or marking indicating the standard used as the basis of design. _____Place proper venting on oil tank: atmospheric and emergency 3405.3.6.2Listed and approved machines. Parts cleaning and degreasing conducted in listed and approved machines in accordance with Section 3405.3.6.1 shall be in accordance with Sections 3405.3.6.2.1 through 3405.3.6.2.7. _____Plug solvent machine into GFI outlet

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00579
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/04/2011 VIOL - BUILDING SVCS & SYSTEMS MPursley Approved All corrections made 3/31/11