Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/07/2011

Applicant:

BROWN GAROLD C FAMILY LTD PARTNERSHIP

Description:

FULL INPSECTION (2 COUNT)

Outstanding Inspections

Case Number: T11FR00574
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
03/07/2011 INSP - FULL JDAVIS Correction Required Main Building 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - TWO EACH 2. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - TIME CLOCK - RUSS'S OFFICE 3. _____ 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system … - 3 EXIT SIGNS IN MAIN BUILDING 4. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied - Emergency light in the hallway 5. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits: - Places of detention or restraint. - In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. - Rear Exit WEST YARD 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 2. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: THERE ARE VARIOUS LOCATIONS AND SITUATION WHERE THE ELCTRICAL WIRING DOES NOT MEET THE ELECTRICAL CODE SUCH AS: - EXTENSION CORDS WITED TO ELECTRICAL PANAL - CORDS THAT ARE DAMAGED ARE BENIG USED - CORDS AS PERMANENT WIRING EAST YARD 1. SECTION 2703.1 - REPLACE THE BUNG IN THE TANK STORED OUTSIDE OR REPLACE THE VENT PIPE BUILDING #2 1. _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. - NORTH EXIT 2. _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. -WEST SIDE OF THE BAY 3. _____ 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. - TEST SPRINKLER SYSTEM AND SENT RESULTS TO THE FIRE DEPARTMENT