Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/03/2011

Applicant:

ARIZONA ACV VI LLC

Description:

99 Cent Store fire inspection.

Outstanding Inspections

Case Number: T11FR00543
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
03/03/2011 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
03/03/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
03/03/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. _____ Mount extinguishers in an approved manner
03/03/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
03/03/2011 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
03/03/2011 VIOL - COMPRESSED GASES JLOYA Violation 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel. *** Secure gas cylinder in an approved manner to avoid accidental dislodgment.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00543
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/29/2011 INSP - REINSPECTION JLOYA Approved Violations abated.