Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/17/2011

Applicant:

WETMORE PLAZA LLC

Description:

Full Fire Prevention Inspection. Paula Noble... 888-3011

Outstanding Inspections

Case Number: T11FR00454
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/17/2011 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. All open spaces in the electrical panel located behind the fron desk shall be properly covered.
02/17/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Repair the leaking fire sprinkler system heads. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
02/17/2011 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Test all emergency lighting units and repair or replace any defective units.
02/17/2011 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The EXIT sign located in the estitition room shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00454
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/14/2011 INSP - FULL JBURGE Approved All noted fire code violations have been corrected.