Case: T11FR00438
Case Details
Entered Date:
02/15/2011
Applicant:
ORB 58 LLC
Description:
El Merendero fryer red tag
Outstanding Inspections
Case Number: T11FR00438
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***A K class extinguisher shall be installed according to this code. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One Class K portable fire extinguisher of a minimum 1.5 gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One additional Class K portable fire extinguisher of a minimum 1.5 gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer's recommendations. ___ Please contact 791 4014 or number behind tag for re-inspection and removal of tag, thank you for your cooperation. |
02/16/2011 | INSP - REINSPECTION | JLOYA | Violation | Violation abated with K class in premises. Red tag removed 2-15-2011 |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00438
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2011 | COMPL - INITIAL INSPECTION | JLOYA | Approved | Red tag placed on fryer due to lack of class K fire extinguisher. Owner stated it might be a week before he gets one. Appliance was turned off by employee and tag was placed inside door. |