Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/10/2011

Applicant:

PARK VIEW PLAZA INC

Description:

99c Store fire inspection.

Outstanding Inspections

Case Number: T11FR00416
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/10/2011 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
02/10/2011 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
02/10/2011 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
02/10/2011 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1.- A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00416
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/10/2011 INSP - REINSPECTION JLOYA Approved Violations abated.