Case: T11FR00374
Case Details
Entered Date:
02/08/2011
Applicant:
RIVAS BLANCA E
Description:
Blanca's Jewlry fire inspection.
Outstanding Inspections
Case Number: T11FR00374
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2011 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 305.1 Clearance from ignition sources. Clearance between ignition sources, such as luminaires, heaters, flame-producing devices and combustible materials, shall be maintained in an approved manner. ___Provide additional sheetrock protection from flames where open flame is used. ___Provide proper exhaust hood to extract fumes. |
| 02/08/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___ Eliminate power strip to power strip situation at front counters. |
| 02/08/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 02/08/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
| 03/03/2011 | INSP - REINSPECTION | JLOYA | Violation | Violations abated. |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00374
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2011 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |