Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/01/2011

Applicant:

DEVELOPING TRADING & TRANSACTING CORP

Description:

Full Fire Prevention Inspection. Mitzi Vantine 319-5642

Outstanding Inspections

Case Number: T11FR00308
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/01/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag all portable fire extinguishers. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
02/01/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____1. Service the kitchen hood extinguishing system.
02/01/2011 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Properly secure the CO2 cylinders located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00308
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/17/2011 INSP - FULL JBURGE Approved All noted Fire code violations have been corrected.