Case: T11FR00246
Case Details
Entered Date:
01/26/2011
Applicant:
UC ASSOCIATES LLC
Description:
FULL INSPECTION
Outstanding Inspections
Case Number: T11FR00246
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2011 | INSP - FULL | jdavis | Correction Required | 1. _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. 2. _____ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. -REAR DOOR SOUTH 3. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: -PLACE BLANKS IN THE ELECTRICAL PANEL -REPLACE THE MISSIGN ELCTRILCA LCOVER UNDER THE ELECTRICAL PANEL 4. _____ 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied -2 EACH 5. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - THROUGHOUT LAST 2009 6. _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. -THE DOOR MAINTAINS A "DOOR" APPEAREANCE. IF THIS IS NOT TO BE A DOOR ALL THE HARDWARE IDENTIFYING IT AS SUCH MUST BE REMOVED. 7. _____ 3405.3.6.2.7 Installation. Machines shall be installed in accordance with their listings. - BE SURE THAT the parts cleaner is not hampered from it's mormal operation. |