Case: T11FR00243
Case Details
Entered Date:
01/26/2011
Applicant:
CHIHONKY LLC
Description:
Branding ron Bar fire inspection.
Outstanding Inspections
Case Number: T11FR00243
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
| 01/26/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 01/26/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8 Door operations. doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
| 01/26/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation. ___Remove sliding bolts from front door. |
| 01/26/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00243
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2011 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 02/16/2011 | INSP - REINSPECTION | JLOYA | Approved | Reinspection done with all violations abated. |