Description:

Full MAITS inspection.

Outstanding Inspections

Case Number: T11FR00239
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
01/26/2011 INSP - FULL BCORRALE Continued Full MAITS inspection of TCC arena, exhibition halls. 1-12-11.
01/26/2011 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued ___Unapproved electrical. - South Ex. Hall door LLC 132. - South Ex. Hall door MLB 212. - Arena floor, west wall. ***Repair electrical.
01/26/2011 VIOL - FIRE RESIST.RATED CONST BCORRALE Continued ___Damaged walls - South Ex. Hall door LLC 132 ***Repair walls.
01/26/2011 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Continued ___Missing Fire Extinguishers. - South Ex. Hall door LLC 129 - South Ex. Hall door LLC 113 ***Replace extinguishers.
01/26/2011 VIOL - MEANS OF EGRESS BCORRALE Continued ___Blocked exit doors. - West arena doors. ***Unblock doors.
01/26/2011 VIOL - MEANS OF EGRESS BCORRALE Continued ___Exit door self closer damaged - West arena area. ***Repair door.
01/26/2011 VIOL - HAZARDOUS MATERIALS,GEN BCORRALE Continued ___Damaged gasoline can. - Service area ***Replace can.
01/26/2011 VIOL - HAZARDOUS MATERIALS,GEN BCORRALE Continued ___Missing secondary containment for oils. - North Ex. Hall ***Clean area, install secondary containment.