Case: T11FR00150
Case Details
Entered Date:
01/13/2011
Applicant:
BERINGHAUSE DANIEL TR
Description:
Full Fire Prevention Inspection Building Rep: Nicole Scheack Phone # 887-0111
Outstanding Inspections
Case Number: T11FR00150
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2011 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
01/13/2011 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 510.1 Identification Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____ Place the wording "RISER ROOM" on riser room door to properly identify the fire service features location. |
01/13/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlets. _____ Place an approved cover over the electrical outlet in your back storage room. |
01/13/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag your buildings sprinkler system or provide the proper records showing that your system has been approved and is current. _____ Replace the missing "FDC" cover |
01/13/2011 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Test your emergency lighting units and fix, repair, or replace any non-working lighting unit(s) in order to meet code standards ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo) |