Case: T11FR00063
Case Details
Entered Date:
01/06/2011
Applicant:
4695 NORTH ORACLE GROUP LLC
Description:
Full Fire Prevention Inspection Building Rep: John Hammond Phone # 748-7100
Outstanding Inspections
Case Number: T11FR00063
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2011 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
| 01/06/2011 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlets. _____ Place approved cover(s) over the electrical outlets |
| 01/06/2011 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance The required fire-resistance-rated construction shall be maintained. Such elements shall be repaired, restored, or replaced when damaged, altered, breached, or penetrated. _____ Fix, repair, or restore all openings or holes in the fire resistive walls ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo) |