Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/04/2011

Applicant:

4695 NORTH ORACLE GROUP LLC

Description:

Full Fire Prevention Inspection. 888-0741

Outstanding Inspections

Case Number: T11FR00024
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
01/04/2011 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord used to power nail station number 2. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
01/04/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag, or remove the portable fire extinguisher.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00024
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/19/2011 INSP - FULL JBURGE Approved All noted Violations have been corrected.