Case: T11FR00023
Case Details
Entered Date:
01/04/2011
Applicant:
CARMAX AUTO SUPERSTORES WEST COAST INC
Description:
Full Fire Prevention Inspection. Abel Rodriguez--- 917-6317
Outstanding Inspections
Case Number: T11FR00023
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2011 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | IFC 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. _____1. Supply new keys for the fire department lock box. |
| 01/04/2011 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | IFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1. Post a the wording "RISER ROOM" on the outside of the riser room door. |
| 01/04/2011 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord located in the lobby. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00023
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2011 | INSP - FULL | JBURGE | Approved | All noted Violations have been corrected. |