Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/04/2011

Applicant:

BARNEY'S VENTURE LLC

Description:

Kappy's - Full inspection done 1/3/2011; Chris Smalligan / Kurt Veitch - owner- 296-9500; A-2 occupancy / C of O on premises-156 persons;

Outstanding Inspections

Case Number: T11FR00018
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
01/04/2011 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations: Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises]
01/04/2011 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip.
01/04/2011 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
01/04/2011 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation Extinguishing system service: 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ______ Hood system to be serviced, tested and tagged every 6 months. 901.6.2 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.
01/04/2011 VIOL - MEANS OF EGRESS BCOBB Violation Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt. [wrought iron door from kitchen and door from pool room]
01/04/2011 VIOL - MEANS OF EGRESS BCOBB Violation Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights.
01/04/2011 VIOL - MEANS OF EGRESS BCOBB Violation Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system.
01/04/2011 VIOL - MEANS OF EGRESS BCOBB Violation Signs over doors:: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______ Re-place above-mentioned sign on or near front door in an approved manner. [and replace others with wrong wording or damage]
01/04/2011 VIOL - COMPRESSED GASES BCOBB Violation Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner. [outside - redo so it is effective, inside - chain or "nest" in a crate so it cannot be upset]

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00018
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/11/2011 INSP - REINSPECTION BCOBB Approved All approved / closed.