Case: T11FR00016
Case Details
Entered Date:
01/03/2011
Applicant:
BJB LLC
Description:
Carol Lighting 12/20/10
Outstanding Inspections
Case Number: T11FR00016
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2011 | VIOL - FIRE SERVICE FEATURES | MPURSLEY | Correction Required | 510.1 Identification Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____ Place the wording "RISER ROOM" on riser room door to properly identify the fire service features location. |
| 01/04/2011 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
| 01/04/2011 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
| 01/04/2011 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00016
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2011 | INSP - REINSPECTION | MPursley | Approved | All corrections made 1/20/11 |