Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/03/2011

Applicant:

SHENITZER DEVELOPMENT COMPANY

Description:

Full Fire Prevention Inspection. Brooke Keith 293-7031

Outstanding Inspections

Case Number: T11FR00013
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/03/2011 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____1. Remove all combustible storage located around the compressor.
01/03/2011 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located by the compressor room door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
01/03/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. All portable fire extinguishers shall be serviced.
01/03/2011 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the south door.

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00013
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/19/2011 INSP - FULL JBURGE Approved All noted Violations have been corrected.