Case: T10FR02715
Case Details
Entered Date:
12/23/2010
Applicant:
REID PARK PROPERTIES LLC
Description:
Double tree fire inspection.
Outstanding Inspections
Case Number: T10FR02715
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2010 | VIOL - FIRE SERVICE FEATURES | JLOYA | Violation | 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. Building < 50 feet from the curb require 12" numbers displayed on the building. Buildings > 50 feet from the curb require 15" numbers displayed on the building. Tenant space numbers shall be 3" Address range may be displayed in 12" numbers on the building. |
| 12/23/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
| 12/23/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 12/23/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 12/23/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. |
| 12/23/2010 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |
| 12/23/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. |
| 12/23/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting |
| 12/23/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02715
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118 Fax 791-5346 Received by________________ |
| 02/02/2011 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |