Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/21/2010

Applicant:

TESORO ENTERPRISES LLC

Description:

FULL INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02696
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/21/2010 INSP - FULL jdavis Approved
12/21/2010 INSP - FULL JDAVIS Approved 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. -THROUGHOUT BUSINESS 2. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - 2 EACH