Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/17/2010

Applicant:

MATZ ENTERPRISES INC

Description:

best buy furniture fire inspection.

Outstanding Inspections

Case Number: T10FR02667
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/17/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118 Fax 791-5346 Received by________________
12/17/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
12/17/2010 VIOL - LIQUID PETROLEUM GASES JLOYA Violation 3803.2.1 Portable containers. Portable LP-gas containers, as defined in NFPA 58, shall not be used in buildings

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02667
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/05/2011 INSP - REINSPECTION JLOYA Approved violationns abated.