Case: T10FR02651
Case Details
Entered Date:
12/15/2010
Applicant:
TNP SRT NORTHGATE PLAZA TUCSON LLC
Description:
SPRINKLER SYSTEM INSPECTION
Outstanding Inspections
Case Number: T10FR02651
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | RSPANGLE | Violation | 1.) TFC 901.6 THE SPRINKLER SYSTEM MUST HAVE AN AUDIBLE WATER FLOW ALARM INSTALLED. |
12/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | RSPANGLE | Violation | 2.) TFC 901.6 THE FREEZERS MUST HAVE SPRINKLER HEADS INSTALLLED. INSTALLATION OF SPRINKLER HEADS REQUIRES APPROVED PLANS AND A PERMIT. |
12/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | RSPANGLE | Violation | 3.) TFC 901.6 REMOVE THE SPIGOT FROM THE INSPECTOR'S TEST VALVE. A PERMIT MUST BE OBTAINED WITHIN 30 DAYS. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02651
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2011 | INSP - FULL | RSPANGLE | Approved | FLOW ALARM WAS REPAIRED. THE WATER SPIGOT WAS REMOVED FROM THE INSPECTOR'S TEST VALVE. NOTE: THIS SPRINKLER SYSTEM WAS INSTALLED UNDER A PREVIOUS CODE WHEN PARTIAL SYSTEMS WERE APPROVED. THIS SYSTEM WAS FOR KITCHEN PROTECTION ONLY AND WAS NOT REQUIRED TO EXTEND INTO OTHER AREAS OF THE BUILDING. THEREFORE SPRINKLER HEADS ARE NOT REQUIRED IN THE WALK-IN COOLERS. |