Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/15/2010

Applicant:

TNP SRT NORTHGATE PLAZA TUCSON LLC

Description:

SPRINKLER SYSTEM INSPECTION

Outstanding Inspections

Case Number: T10FR02651
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/15/2010 VIOL - FIRE PROTECTION SYSTEMS RSPANGLE Violation 1.) TFC 901.6 THE SPRINKLER SYSTEM MUST HAVE AN AUDIBLE WATER FLOW ALARM INSTALLED.
12/15/2010 VIOL - FIRE PROTECTION SYSTEMS RSPANGLE Violation 2.) TFC 901.6 THE FREEZERS MUST HAVE SPRINKLER HEADS INSTALLLED. INSTALLATION OF SPRINKLER HEADS REQUIRES APPROVED PLANS AND A PERMIT.
12/15/2010 VIOL - FIRE PROTECTION SYSTEMS RSPANGLE Violation 3.) TFC 901.6 REMOVE THE SPIGOT FROM THE INSPECTOR'S TEST VALVE. A PERMIT MUST BE OBTAINED WITHIN 30 DAYS.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02651
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/09/2011 INSP - FULL RSPANGLE Approved FLOW ALARM WAS REPAIRED. THE WATER SPIGOT WAS REMOVED FROM THE INSPECTOR'S TEST VALVE. NOTE: THIS SPRINKLER SYSTEM WAS INSTALLED UNDER A PREVIOUS CODE WHEN PARTIAL SYSTEMS WERE APPROVED. THIS SYSTEM WAS FOR KITCHEN PROTECTION ONLY AND WAS NOT REQUIRED TO EXTEND INTO OTHER AREAS OF THE BUILDING. THEREFORE SPRINKLER HEADS ARE NOT REQUIRED IN THE WALK-IN COOLERS.