Description:

E & F Transmission fire inspection.

Outstanding Inspections

Case Number: T10FR02611
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/10/2010 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. Building < 50 feet from the curb require 12" numbers displayed on the building. Buildings > 50 feet from the curb require 15" numbers displayed on the building. Tenant space numbers shall be 3" Address range may be displayed in 12" numbers on the building.
12/10/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used.
12/10/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
12/10/2010 VIOL - MOTOR FUEL DISPENSING JLOYA Violation 2211.2.1 Cleaning of parts. Cleaning of parts shall be conducted in listed and approved parts-cleaning machines
12/10/2010 VIOL - HAZARDOUS MATERIALS,GEN JLOYA Violation TFC 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02611
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/10/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118 Fax 791-5346 Received by________________
02/23/2011 INSP - REINSPECTION JLOYA Approved Violations abated.