Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/09/2010

Applicant:

CAMPBELL AVENUE SHOPPING CENTER LLC

Description:

Baggins 12/6/10

Outstanding Inspections

Case Number: T10FR02590
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
12/09/2010 VIOL - FIRE RESIST.RATED CONST MPursley Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile _____ Fix and repair all openings or holes in the ceiling
12/09/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code
12/09/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. _____Maintain minimum aisle width
12/09/2010 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02590
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/05/2011 COMPL - REINSPECTION MPursley Approved All corrections made 1/4/11. Property Management is goig to take care of exit hallway T11FR00038.