Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/07/2010

Applicant:

CARPER BRUCE M & YVONNE M CP/RS

Description:

Full Fire Prevention Inspection Building Rep: Bruce Carper Phone # 888-5955

Outstanding Inspections

Case Number: T10FR02583
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
12/07/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
12/07/2010 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the southeast egress door, as bolt lock of any kind are not permitted ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you.