Case: T10FR02551
Case Details
Entered Date:
12/06/2010
Applicant:
JONATHAN S RESTAURANT LLC
Description:
Full inspection done 12/6/2010; A-2 Occupancy; Rovella Ruscitti - Manager; John Landeen - owner / 296-1631;
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02551
Case Description: INSPECTION
Total Completed Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | VIOL - COMPRESSED GASES | BCOBB | Approved | Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner. |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Exit signs: TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ______Place exit signs in an approved manner over the patio gate. |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). ______ Repair exit door to comply with 15lb force requirement. At no time should this door be locked from the inside - [replace the panic hardware.] ______ Install approved panic hardware to the patio exit. No other locks, chains or bolt locks are allowed on this door. If, in the future locks are found on this gate a citation may be issued requiring a court appearance and probable fines. |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Keyed main entry: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______ Place above-mentioned sign on or near front door in an approved manner. [Two doors - Front iron , and front wooden] Note: the chain on the front gate must be removed when building is occupied. The other doors may not have any chain at all. |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt lock. [Gate] |
| 12/06/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Exit access, exit, and discharge path blocked: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. ______ Clear exit path and keep it clear [36" minimum] -table blocking exit. |
| 12/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises] ______ Explain the wires attached to the system [Red wires in Dry storage closet, and wires in the front of the restaurant by the bar tables. |
| 12/06/2010 | VIOL - INT.FINISH, DEC. MATL'S | BCOBB | Approved | Christmas Tree: SECTION 806 DECORATIVE VEGETATION IN NEW AND EXISTING BUILDINGS 806.1 Natural cut trees. Natural cut trees, where allowed by this section, shall have the trunk bottoms cut off at least 0.5 inch (12.7 mm) above the original cut and shall be placed in a support device complying with Section 806.1.2. 806.1.1 Restricted occupancies. Natural cut trees shall be prohibited in Group A, E, I-1, I-2, I-3, I-4, M, R-1, R-2 and R-4 occupancies. Exceptions: 1. Trees located in areas protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 shall not be prohibited in Groups A, E, M, R-1 and R-2. 2006 INTERNATIONAL FIRE CODEĀ® 61 2. Trees shall be allowed within dwelling units in Group R-2 occupancies. 806.1.2 Support devices. The support device that holds the tree in an upright position shall be of a type that is stable and that meets all of the following criteria: 1. The device shall hold the tree securely and be of adequate size to avoid tipping over of the tree. 2. The device shall be capable of containing a minimum two-day supply of water. 3. The water level, when full, shall cover the tree stem at least 2 inches (51 mm). The water level shall be maintained above the fresh cut and checked at least once daily. 806.1.3 Dryness. The tree shall be removed from the building whenever the needles or leaves fall off readily when a tree branch is shaken or if the needles are brittle and break when bent between the thumb and index finger. The tree shall be checked daily for dryness. 806.2 Artificial vegetation. Artificial decorative vegetation shall meet the flame propagation performance criteria of NFPA 701. Meeting the flame propagation performance criteria of NFPA 701 shall be documented and certified by the manufacturer in an approved manner. 806.3 Obstruction of means of egress. The required width of any portion of a means of egress shall not be obstructed by decorative vegetation. 806.4 Open flame. Candles and open flames shall not be used on or near decorative vegetation. Natural cut trees shall be kept a distance from heat vents and any open flame or heat-producing devices at least equal to the height of the tree. 806.5 Electrical fixtures and wiring. The use of unlisted electrical wiring and lighting on natural cut trees and artificial decorative vegetation shall be prohibited. The use of electrical wiring and lighting on artificial trees constructed entirely of metal shall be prohibited. ______ Remove cut tree and replace with an approved artificial one if desired. |
| 12/06/2010 | VIOL - PRECAUTION AGAINST FIRE | BCOBB | Approved | Housekeeping: TFC 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. ______Remove all storage, bicycles, clothing etc from around the water heater. |
| 12/06/2010 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises] |