Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/01/2010

Applicant:

COMMERCIAL NET LEASE REALTY INC

Description:

Full inspection done 11/30/2010; Tom Palomares 722-4302; A2 Occupancy;

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02534
Case Description: INSPECTION
Total Completed Inspections - 16
End Date Description Inspector Results Comments
12/01/2010 VIOL - COMPRESSED GASES BCOBB Approved Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner.
12/01/2010 VIOL - MEANS OF EGRESS BCOBB Approved Keyed entry: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______ Place above-mentioned sign on or near patio door in an approved manner.
12/01/2010 VIOL - MEANS OF EGRESS BCOBB Approved Patio door - status: 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a Group Aor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. ______ Until notified differently the Patio door with the Exit sign must be unlocked anytime the building is occupied. If the door is found locked while occupied a citation may be issued requiring a court appearance and probable fines. The business may be required to put a panic hardware opener on this door per the Fire marshal after further review.
12/01/2010 VIOL - MEANS OF EGRESS BCOBB Approved Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights.
12/01/2010 VIOL - MEANS OF EGRESS BCOBB Approved Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system.
12/01/2010 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Hood needs cleaning: 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ______ Clean hood in an acceptable manner and maintain it this way.
12/01/2010 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Hood system: 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ______ Hood system to be serviced, tested and tagged every 6 months. Hood system coverage: 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ______ Hood system to be checked to make sure the appliances are covered properly.
12/01/2010 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. [K class, ABC]
12/01/2010 VIOL - FIRE RESIST.RATED CONST BCOBB Approved Missing, Damaged or Moved ceiling tiles: TFC2006/ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing or damaged ceiling tiles.
12/01/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires.
12/01/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Multiplug adapters: TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices.
12/01/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner.
12/01/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip.
12/01/2010 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Sterno left uncovered and leaking: TFC 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. A vacant structure which is not secured against unauthorized entry as required by Section 311 shall be deemed unsafe. ______ Cap all sterno and keep from soaking or spilling area.
12/01/2010 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Clearance below ceiling: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 24 inches or more below ceiling.
12/01/2010 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code violations: Notes: ************************************************************************ FYI- 901.6.2 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ******************************************************************** 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, inspected and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises]