Case: T10FR02532
Case Details
Entered Date:
12/01/2010
Applicant:
SHEPPARD LLC
Description:
FULL FIRE INPSECTION
Outstanding Inspections
Case Number: T10FR02532
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2010 | VIOL - PRECAUTION AGAINST FIRE | WMOTTO | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1___ NEED TO ASSURE ALL BOXES IN WAREHOUSE ARE 18 INCHES BELOW SPRINKLER HEADS. |
| 12/01/2010 | VIOL - FIRE SERVICE FEATURES | WMOTTO | Correction Required | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10. Access doors for high-piled combustible storage shall comply with Section 2306.6.1. 1___ NEED TO POST SIGN OVER DOORS ON EAST WALL ON EXTERIOR STATING DOOR BLOCKED. NOT MIDDLE DOOR. |
| 12/01/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ NEED TO HAVE ALL DEFICIENCIES REPAIRED FROM LAST SPRINKLER INSPECTION. |
| 12/01/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface- mounted hardware. 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 1___ NEED TO REMOVE DROP BARS AND HARDWARE ON DOOR ON SOUTH WALL IN WAREHOUSE WITH EXIT SIGN. 2___ NEED TO REMOVE DROP BAR AND HARDWARE ON MIDDLE DOOR ON EAST WALL. |
| 12/01/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ EXIT SIGN NEEDS TO BE FIXED ON EAST WALL OVER DOOR IN WAREHOUSE NOT LIGHTING UP UPON TESTING. 2___ EXIT SIGN OVER MAIN DOORS NOT WORKING ALSO DO NOT LIGHT UP UPON TESTING. |
| 12/01/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ NEED TO INSTALL AN ILLUMINATED EXIT SIGN OVER MIDDLE DOOR ON EAST WALL IN WAREHOUSE. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02532
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2010 | INSP - FULL | WMOTTO | Approved | ALL VIOLATIONS ABATED. |