Case: T10FR02529
Case Details
Entered Date:
11/30/2010
Applicant:
MARLEE SAGUARO LLC
Description:
Full inspection done 11/29/2010; Krystal Garrett - 290-6892; A-2 occupancy;
Outstanding Inspections
Case Number: T10FR02529
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2010 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code violations: |
| 11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. |
| 11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Multiplug adapters: TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices. |
| 11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Tape on breakers: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _______ Remove tape from breakers. |
| 11/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Extinguishers not mounted: TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. |
| 11/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Hood system coverage: 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ______ Hood system to be checked to make sure the appliances are covered properly. |
| 11/30/2010 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
| 11/30/2010 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. [sideline bar]. |
| 11/30/2010 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Keyed main entry: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______ Place above-mentioned sign on or near front door in an approved manner. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02529
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2010 | VIOL - COMPRESSED GASES | BCOBB | Approved | Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner. [Please make sure they are not only chained together, but that they are chained to the wall also.] |
| 03/11/2011 | INSP - REINSPECTION | BCOBB | Approved | All approved / closed |