Description:

Full Fire Prevention Inspection Building Rep: Phone # 408-3131

Outstanding Inspections

Case Number: T10FR02479
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/24/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
11/24/2010 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlets. _____ Place an approved cover over the electrical outlet (west wall lobby)
11/24/2010 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards
11/24/2010 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the rear egress door, as bolt lock of any kind are not permitted 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions hindering the use, the path, or the activity of the egress door and be sure to always maintain a clear and obstruction free path to your rear egress door.
11/24/2010 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)