Case: T10FR02457
Case Details
Entered Date:
11/23/2010
Applicant:
GIBSON FAMILY LLC
Description:
The drawing studio complaint.
Outstanding Inspections
Case Number: T10FR02457
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. ___Exit path and door operation at rear of art studio is being blocked by a COX communications box. |
Completed Inspections
Case Status: FIELD
Case Number: T10FR02457
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2010 | COMPL - INITIAL INSPECTION | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. |