Entered Date:

11/19/2010

Applicant:

CAMPBELL AVENUE SHOPPING CENTER LLC

Description:

Pakmail 11/16/10

Outstanding Inspections

Case Number: T10FR02430
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
11/19/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep hot water heater clear. 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
11/19/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02430
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/07/2010 COMPL - REINSPECTION MPursley Approved All corrections made 12/6/10