Description:

Full Fire Prevention Inspection Chris Martinez 292-6330

Outstanding Inspections

Case Number: T10FR02412
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/17/2010 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 508.5.4- 1. Remove all storage located around the sprinkler system riser pipe and control valves. 2. Remove the semi trainler obstructing access to the sprinkler system FDC.
11/17/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5- Remove the extension cord used to power the water cooler located in the break room.
11/17/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6- Repair all noted deficiencies on the annual sprinkler system inspection report.
11/17/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5- Test all lighting units and exit signs for emergency back-up power. Repair or replace any defictive units or exit signs.
11/17/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.2- 1. Remove all storage from obstructing the southeast exit door. 2. Remove all storge from obstructing the east door located in the dock area. NOTE: The east gate shall not be locked when the building is occupied.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02412
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/17/2010 INSP - FULL JBURGE Approved Correct all noted Tucson Fire Code violations.