Case: T10FR02412
Case Details
Entered Date:
11/17/2010
Applicant:
SAMPSON JAMES K & BARBARA L TR
Description:
Full Fire Prevention Inspection Chris Martinez 292-6330
Outstanding Inspections
Case Number: T10FR02412
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2010 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | IFC 508.5.4- 1. Remove all storage located around the sprinkler system riser pipe and control valves. 2. Remove the semi trainler obstructing access to the sprinkler system FDC. |
11/17/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5- Remove the extension cord used to power the water cooler located in the break room. |
11/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6- Repair all noted deficiencies on the annual sprinkler system inspection report. |
11/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5- Test all lighting units and exit signs for emergency back-up power. Repair or replace any defictive units or exit signs. |
11/17/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.2- 1. Remove all storage from obstructing the southeast exit door. 2. Remove all storge from obstructing the east door located in the dock area. NOTE: The east gate shall not be locked when the building is occupied. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02412
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2010 | INSP - FULL | JBURGE | Approved | Correct all noted Tucson Fire Code violations. |