Case: T10FR02404
Case Details
Entered Date:
11/17/2010
Applicant:
SABINO-VERDE LLC
Description:
Ful inspection done 11/12/2010; A-2 occupancy; Shahril Noorhizan- Manager, 886-8619;
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02404
Case Description: INSPECTION
Total Completed Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2010 | VIOL - COMPRESSED GASES | BCOBB | Approved | Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner. All approved - Good Job! closed. |
11/17/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
11/17/2010 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |
11/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | TFC2006/ 906.5 Conspicuous Location- extinguisher: TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount a tagged and approved "ABC" extinguisher in the area behind the kitchen, on the back wall. TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. |
11/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Hood system: 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ______ Hood system to be serviced, tested and tagged every 6 months. |
11/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. [k class extinguisher in kitchen] |
11/17/2010 | VIOL - FIRE RESIST.RATED CONST | BCOBB | Approved | Missing, Damaged or Moved ceiling tiles: TFC2006/ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing or damaged ceiling tiles. |
11/17/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. [outlet behind serving line] |
11/17/2010 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: |