Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/12/2010

Applicant:

PARK MALL LLC

Description:

Full Inspection conducted 11/12/10 I have received a copy of this report and understand the corrections needed: ______________ Business Rep.: Paul Lakers Phone: 514-9665 Inspector: _________________, David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after) Certificate of Occupancy: ON FILE A-3, OL=245 Park Mall sprinkler system last inspection noted 8/08 Hood tagged 8/10, by Benson, DEFICIENCIES Provide and retain copies of system inspection reports.

Outstanding Inspections

Case Number: T10FR02393
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/12/2010 INSP - FULL dgreenl1 Violation Please correct the following Tucson Fire Code violations: TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. Correct deficiencies noted in Benson Systems inv#B008623002 _____ System protection line does not cover appliances _____ Repair/replace nozzles due to grease build-up _____ Test all lighted EXIT signs and emergency egress lighting and repair/replace as necessary _____ Replace drip pans for all hood systems TFC 904.11.6.2 - Grease extractors. Where grease extractors are installed, they shall be operated when the commercial- type cooking equipment is used. _____ Remove all gaps in hood system baffles and, if necessary, clean system iwhere gaps have allowed the passage and accumulation of grease. Chapter 906 - Portable Fire Extinguishers TFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.) _____ K-Class extinguisher shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____ Repair bracket and mount K-Class extinguisher TFC 904.11.6.3 - Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean hood system and keep records of periodical cleanings. _____ Clean fryers _____ Clean drip pans under wok TFC 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____ Replace missing ceiling tiles. TFC 605.5 - Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ remove extension cord serving bug light TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around transformer

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02393
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/23/2011 INSP - REINSPECTION dgreenl1 Approved all noted deficiencies corrected