Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/10/2010

Applicant:

EL GANADO LTD PARTNERSHIP

Description:

Full inspection done 11/10/2010; "S-1" occupancy; Lon Pierce- Manager - 749-0248; Mike Garratt.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02388
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
11/10/2010 VIOL - MEANS OF EGRESS BCOBB Approved Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt. [both doors leading out of garage area]
11/10/2010 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. [If new attach a copy of the receipt to extinguisher for the first year]
11/10/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. [Garage area- far wall]
11/10/2010 VIOL - ADMINISTRATION BCOBB Approved OIL tanks: Permits and Venting- 105.6.16 Flammable and combustible liquids. An operational permit is required: 1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the Department of Transportation (DOTn) nor does it apply to piping systems. 2. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following: 2.1. The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, unless such storage, in the opinion of the code official, would cause an unsafe condition. 2.2. The storage or use of paints, oils, varnishes or similar flammable mixtures when such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days. 3. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. [SEE TFC MODIFICATION BELOW] 4. To remove Class I or Class II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes. 5. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. Modification: Section 105.6.16 #3 Flammable and combustible liquids. Is hereby AMENDED by ADDING the words "or Class IIIB" after the word "Class IIIA." ______ Provide proof of permit, and proper venting of oil storage tanks. [Contact Conrad Funke of TFD @ 791-4502] *****************************************************************************
11/10/2010 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site.